Success message
Error message
Fire Alarm Control Panels (FACPs) typically include three key relay outputs:
Alarm
Supervisory
Fault
Each relay operates electrically isolated from the rest of the FACP’s electronics. When a specific condition is detected (like fire, maintenance issue, or system fault), the relay changes state to send a signal to external systems.
A relay inside an FACP is like a remote-controlled switch. It has three terminals: Common (C)
Normally Open (NO)
Normally Closed (NC)
A small electromagnet activates the relay to switch the connection between terminals:
At rest: C is connected to NC
When energised: C switches to NO
These contacts are used to control other equipment or send signals out to other systems like monitoring stations.
Purpose: Sends a fire alarm signal to external systems (like monitoring panels or emergency response systems).
Behaviour:
Alarm light turns on → Relay activates → C → NO
Stays active until alarm resets
Common uses:
Notifying central stations
Closing fire doors
Shutting down HVAC
Releasing magnetic door locks
Activating the AOV system
Grounding the lift
Supervisory Relay Output:
Purpose:
Sends a signal for non-emergency conditions like valve tamper or pump running.
Behavior:
Normal: C → NC
Supervisory event active:
Amber light turns on → Relay activates → C → NO Supervisory alarms are informational. They typically don’t cause building evacuation or fire department dispatch.
Purpose:
Indicates faults in the FACP such as open circuits, power loss, or component failures.
Behaviour:
Normal (no trouble): Relay is active → C → NO
Trouble condition: Yellow trouble light → Relay deactivates → C → NC Why this relay is “weird”: It is designed to be normally active so that if the panel loses power or dies completely, the relay drops out — signaling a problem even when the panel can’t.
Some older or proprietary panels may use relays differently. Always refer to the FACP manual to verify relay behavior before installation or troubleshooting.
Here’s a diagram that visually explains how the three relays work:
Always Check the Manual
While most modern Fire Alarm Control Panels follow standard relay behaviours, older or specialised panels may differ. Always consult the FACP’s instruction manual before wiring or programming relay outputs.
Understanding how relays work is just the beginning. Take the next step with hands-on training through our UK Ofqual-Approved Fire Alarm Courses. Whether you're starting out or refining your expertise, these accredited courses provide the practical skills and certification needed for real-world fire alarm installation, maintenance, and commissioning.
Click here for more information. Courses

LFS
Phone 03330064005
Address Riverside Centre, Dickens Road, Gravesend, Kent, DA12 2JY